York G8C05012(MU,MD)B12: Text of Technical Manual

(Ocr-Read Version Summary of Contents, UPD: 02 March 2024)
  • TECHNICAL GUIDE

    80 AFUE

    MULTI-POSITION

    GAS FURNACES

    MODELS: G8C SERIES

    4-POSITION

    50-125 MBH INPUT

    3-POSITION

    150 MBH INPUT

    EFFICIENCY

    RATING

    CERTIFIED

    ISO 9001

    Certified Quality

    Management System

    270844-YTG-A-0407

    FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

    ®

    DESCRIPTION

    These compact units (31-1/2" high) employ induced combus-

    tion, reliable electronic ignition and high heat transfer heat

    exchangers. The units may be factory shipped for upflow/hor-

    izontal application and converted for downflow application.

    These units may also be factory shipped for downflow appli-

    cation and converted for upflow/horizontal applications

    Note: The 150 MBH input model is upflow/horizontal only and

    may not be converted to the downflow position.

    These furnaces are designed for residential installation in a

    basement, closet, alcove, attic, or garage. All units are factory

    assembled, wired and tested to assure safe dependable and

    economical installation and operation.

    These units are Category I listed and may be common vented

    with another gas appliance as allowed by the National Fuel

    Gas Code.

    WARRANTY

    20-year limited warranty on the heat exchanger.

    5-year limited parts warranty.

    FEATURES

    • 4-position (MU) upflow models allow horizontal-left, hori-

    zontal-right, downflow and convertible applications

    • 4-position (MD) models allow downflow and convertible

    upflow/horizontal applications

    • 3-position (UH) 150 MBH input model allows upflow, hori-

    zontal-left and horizontal-right application

    • Reliable, hot surface ignitor

    • Integrated control module for simplicity and reliable, eco-

    nomical operation

    • Built-in self-diagnostics with fault code display

    • 100% shut off main gas valve for added safety

    • Rollout safety control

    • Low unit amp requirement for easy application

    • High quality inducer motor for quiet operation

    • 40 VA, fuse protected control transformer

    • Terminals for controlling humidifiers and EAC’s

    • Easy to connect power and control wiring

    • Efficiency ratings of 80 AFUE

    • Cooling blower relay supplied for easy installation of add-

    on cooling

    • Blower off-delay for cooling SEER improvement

    • Multi-speed PSC, direct-drive blower motors to match

    cooling requirements

    • Adjustable fan-off settings to eliminate "cold-blow"

    • Compact 31-1/2-in height allows installation in small space

    confines

    • All models are propane convertible with factory kit

    • Pre-painted exterior provides attractive, durable finish

    • Models are not approved for LoNox applications

  • 270844-YTG-A-0407

    2 Unitary Products Group

    DOWNFLOW

    UPFLOW

    A

    A

    B

    E

    D

    BOTTOM VIEW

    F

    G

    29-3/4

    29-3/4

    C

    31-1/2

    31-1/2

    14

    BOTTOM VIEW

    H

    J

    16-1/4

    K

    K

    CABINET AND DUCT DIMENSIONS

    BTUH (kW)

    Input

    Nominal

    CFM

    Cabinet

    Size

    Cabinet Dimension

    A(in.) B(in.) C(in.) D(in.) E(in.) F(in.) G(in.) H(in.) J(in.) K Vent (in.)

    G8C05012(MU,MD)B12

    1

    1200 B 17 1/2 16 1/2 20 3/8 20.0 16 14 3/4 18 3/4 15 1/8 19.0 3

    G8C07512(MU,MD)B12

    1

    1200 B 17 1/2 16 1/2 20 3/8 20.0 16 14 3/4 18 3/4 15 1/8 19.0

    4

    2

    G8C07516(MU,MD)C12

    1

    1600 C 21 20 20 3/8 20.0 19 1/2 18 1/4 18 3/4 18 5/8 19.0

    4

    2

    G8C10016(MU,MD)C12

    1

    1600 C 21 20 20 3/8 20.0 19 1/2 18 1/4 18 3/4 18 5/8 19.0

    4

    2

    G8C10020(MU,MD)D11

    1

    2000 D 24.5 23 1/2 20 3/8 20.0 23 21 3/4 18 3/4 22 1/8 19.0

    4

    2

    G8C12520(MU,MD)D11

    1

    2000 D 24.5 23 1/2 20 3/8 20.0 23 21 3/4 18 3/4 22 1/8 19.0

    5

    2

    G8C15020UHD11

    3

    2000 D 24 1/2 23 1/2 20 3/8 20.0 23 21 3/4 18 3/4 22 1/8 19.0

    5

    2

    1. 4-position models may be factory configured as upflow (MU) or downflow (MD).

    2. 3-position 150 MBH model available only in upflow/horizontal (UH) configuration.

    4. Dimensions “B”, “C”, “D”, and “E” are with duct flanges turned up. “F”, “G”, “H”, & “J” are with flanges flat.

    3. All models are supplied with 3” (7.62 cm) vent connections. An installer supplied transition to 4” (10.16 cm) or 5” (12.7 cm) must be used where necessary.

  • 270844-YTG-A-0407

    Unitary Products Group 3

    Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.

    Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.

    Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.

    RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS

    Models

    Input Output Nominal Airflow Cabinet Width

    Total

    Unit

    AFUE

    Air Temp.

    Rise

    MBH MBH CFM In. Amps °F

    G8C05012(MU,MD)B12 50 40 1200 17-1/2 8.0 80.0 30-60

    G8C07512(MU,MD)B12 75 60 1200 17-1/2 8.0 80.0 35-65

    G8C07516(MU,MD)C12 75 60 1600 21 11.4 80.0 30-60

    G8C10016(MU,MD)C12 100 80 1600 21 11.4 80.0 40-70

    G8C10020(MU,MD)D11 100 80 2000 24 1/2 11.3 80.0 35-65

    G8C12520(MU,MD)D11 125 100 2000 24 1/2 11.3 80.0 40-70

    G8C15020UHD11 150 120 2000 24 1/2 11.3 80.0 40-70

    Models

    Input

    Max. Outlet

    Air Temp

    Blower

    Blower

    Size

    Max

    Over-current

    protect

    Min.Wire Size

    (awg) @ 75 ft.

    one way

    Operation

    Wt.

    MBH °F Hp Amps In. LBS

    G8C05012(MU,MD)B12 50 160 1/2 7.0 10 x 8 15 14 112

    G8C07512(MU,MD)B12 75 165 1/2 7.0 10 x 8 15 14 118

    G8C07516(MU,MD)C12 75 160 1/2 10.4 10 x 10 15 14 129

    G8C10016(MU,MD)C12 100 170 1/2 10.4 10 x 10 15 14 135

    G8C10020(MU,MD)D11 100 165 1 10.3 (2)10 x 6 15 14 149

    G8C12520(MU,MD)D11 125 170 1 10.3 (2)10 x 6 15 14 155

    G8C15020UHD11 150 170 1 10.3 (2)10 x 6 15 14 165

  • 270844-YTG-A-0407

    4 Unitary Products Group

    BLOWER PERFORMANCE

    BTU/H (kW)

    Input

    Cabinet

    Size

    Speed

    Tap

    External Static Pressure, Inches WC - CFM

    0.10.20.30.40.50.60.70.8

    UPFLOW, SINGLE SIDE RETURN (WITHOUT FILTER)

    G8C05012(MU,MD)B12

    1

    B

    High 1411 1360 1289 1218 1154 1075 983 882

    Med 1213 1177 1134 1085 1022 960 880 782

    Low 887 884 871 848 814 775 726 656

    G8C07512(MU,MD)B12

    1

    B

    High 1535 1470 1408 1343 1275 1202 1115 1014

    Med 1215 1199 1182 1151 1106 1039 976 887

    Low 875 874 864 847 827 799 736 658

    G8C07516(MU,MD)C12

    1

    C

    High 1792 1724 1630 1552 1462 1367 1264 1152

    Med 1597 1555 1496 1444 1372 1287 1190 1086

    Low 1115 1140 1167 1183 1149 1093 1023 939

    G8C10016(MU,MD)C12

    1

    C

    High 1868 1781 1690 1600 1498 1396 1277 1156

    Med 1602 1553 1503 1447 1376 1287 1181 1060

    Low 1147 1147 1147 1147 1132 1078 1009 918

    G8C10020(MU,MD)D11

    2

    D

    High

    NOT ALLOWED

    Med-High

    Med-Low

    Low

    G8C12520(MU,MD)D11

    3

    D

    High

    Med-High

    Med-Low

    Low

    G8C15020UHD11

    2

    D

    High

    Med-High

    Med-Low

    Low

    DUAL RETURN (TWO SIDES OR ONE-SIDE & BOTTOM)

    G8C05012(MU,MD)B12

    1

    B

    High 1507 1433 1371 1300 1223 1132 1040 938

    Med 1239 1215 1175 1144 1085 1012 938 838

    Low 907 907 891 875 849 800 741 672

    G8C07512(MU,MD)B12

    1

    B

    High 1634 1562 1484 1417 1340 1238 1154 1030

    Med 1243 1228 1214 1184 1133 1079 999 912

    Low 886 886 886 886 865 823 777 700

    G8C07516(MU,MD)C12

    1

    C

    High 1978 1896 1803 1693 1589 1478 1366 1235

    Med 1682 1657 1606 1530 1455 1366 1265 1137

    Low 1235 1235 1235 1235 1198 1154 1083 987

    G8C10016(MU,MD)C12

    1

    C

    High 2122 2027 1916 1821 1717 1590 1462 1312

    Med 1667 1696 1656 1597 1523 1438 1330 1191

    Low 1130 1145 1177 1194 1181 1146 1077 982

    G8C10020(MU,MD)D11

    2

    D

    High 2350 2248 2129 2015 1876 1745 1596 1425

    Med-High 2122 2018 1926 1824 1722 1606 1458 1311

    Med-Low 1958 1875 1782 1690 1608 1491 1364 1213

    Low 1820 1757 1664 1594 1506 1405 1287 1137

    G8C12520(MU,MD)D11

    2

    D

    High 2483 2392 2282 2161 2032 1887 1739 1567

    Med-High 2198 2123 2039 1930 1830 1708 1550 1413

    Med-Low 1999 1916 1859 1778 1684 1576 1451 1315

    Low 1832 1775 1709 1642 1556 1450 1335 1209

    G8C15020UHD11

    2

    D

    High 2570 2462 2361 2244 2128 1983 1826 1655

    Med-High 2205 2105 2033 1952 1865 1738 1617 1459

    Med-Low 1993 1931 1869 1880 1708 1590 1485 1330

    Low 1831 1782 1722 1660 1575 1477 1364 1231

  • 270844-YTG-A-0407

    Unitary Products Group 5

    RETURN AIR AND FILTERS

    The return air ducts to the furnace must have a total cross

    sectional area of not less than two square inches per 1000

    BTUH of furnace input rating for heating operation. If air con-

    ditioning is to be installed with the furnace, or if it may be

    added at a later time, larger return air ducts may be

    required, depending on the capacity of the air condi-

    tioner and the airflow required.

    FILTER PERFORMANCE

    The airflow capacity data published in the “Blower Perfor-

    mance” table listed above represents blower performance

    WITHOUT filters. To determine the approximate blower per-

    formance of the system, apply the filter drop value for the fil-

    ter being used or select an appropriate value from the “Filter

    Performance” table shown.

    The filter pressure drop values in the “Filter Performance”

    table shown are typical values for the type of filter listed and

    should only be used as a guideline. Actual pressure drop rat-

    ings for each filter type vary between filter manufacturers.

    BOTTOM/END RETURN

    G8C05012(MU,MD)B12

    1

    B

    High 1419 1357 1297 1212 1131 1050 942 846

    Med 1221 1185 1145 1092 1036 961 879 780

    Low 920 902 883 860 818 761 711 639

    G8C07512(MU,MD)B12

    1

    B

    High 1552 1491 1420 1348 1271 1185 1080 970

    Med 1229 1237 1198 1164 1105 1039 956 861

    Low 889 892 879 866 846 807 760 689

    G8C07516(MU,MD)C12

    1

    C

    High 1946 1862 1775 1620 1518 1409 1291 1160

    Med 1683 1611 1551 1484 1388 1300 1190 1080

    Low 1110 1138 1175 1190 1175 1126 1041 937

    G8C10016(MU,MD)C12

    1

    C

    High 1997 1920 1822 1723 1620 1500 1355 1211

    Med 1728 1679 1635 1556 1465 1359 1249 1117

    Low 1131 1156 1181 1190 1171 1126 1049 926

    G8C10020(MU,MD)D11

    2

    D

    High 2327 2232 2121 1999 1888 1763 1628 1473

    Med-High 2050 1967 1868 1757 1658 1525 1403 1260

    Med-Low 1911 1839 1758 1675 1593 1468 1340 1189

    High 1780 1712 1642 1566 1465 1366 1249 1094

    G8C12520(MU,MD)D11

    2

    D

    High 2397 2304 2192 2063 1955 1822 1678 1521

    Med-High 2151 2063 1977 1881 1774 1652 1528 1377

    Med-Low 1972 1906 1838 1748 1660 1551 1419 1282

    Low 1845 1794 1721 1646 1559 1451 1344 1208

    G8C15020UHD11

    2

    D

    High 2488 2389 2276 2151 2024 1883 1730 1577

    Med-High 2164 2084 2024 1920 1816 1692 1558 1395

    Med-Low 1998 1934 1868 1773 1673 1567 1445 1294

    Low 1843 1793 1728 1653 1553 1453 1328 1192

    1. Return air is through side opposite motor (left side) for one side return (worst case).

    2. Airflows above 1800 CFM (50.97 m

    3

    /min) require either return from two sides or one side plus bottom

    3. Airflows expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m

    3

    /min).

    BLOWER PERFORMANCE (CONTINUED)

    BTU/H (kW)

    Input

    Cabinet

    Size

    Speed

    Tap

    External Static Pressure, Inches WC - CFM

    0.10.20.30.40.50.60.70.8

    For applications requiring more than 1800 CFM, it

    is required to use the bottom return, both side

    returns or one side plus the bottom return.

    • Single side return is not approved on 5 Ton mod-

    els.

    • 18” minimum height for return air box for bottom

    return only on Heating only applications with fur-

    nace in the upflow configuration.

    • 24” minimum height for return air box for bottom

    return only on A/C applications with furnace in

    the upflow configuration.

  • 270844-YTG-A-0407

    6 Unitary Products Group

    NOTES:

    1. Air velocity through throwaway type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.

    2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.

    RECOMMENDED FILTER SIZE

    UPFLOW

    Models

    Input Air Flow

    Cabinet

    Size

    Side

    Return

    Bottom/End

    Return

    MBH CFM in. in.

    G8C05012(MU,MD)B12 50 1200 B 25 x 16 25 x 16

    G8C07512(MU,MD)B12 75 1200 B 25 x 16 25 x 16

    G8C07516(MU,MD)C12 75 1600 C 25 x 16 25 x 20

    G8C10016(MU,MD)C12 100 1600 C 25 x 16 25 x 20

    G8C10020(MU,MD)D11 100 2000 D (2) 25 x 16 24 x 24

    G8C12520(MU,MD)D11 125 2000 D (2) 25 x 16 24 x 24

    G8C15020UHD11 150 2000 D (2) 25 x 16 24 x 24

    DOWNFLOW

    Models

    Input Air Flow

    Cabinet

    Size

    Top Return (Downflow)

    Cleanable Air Filters

    Top Return (Downflow)

    Disposable Air Filters

    MBH CFM in. in.

    G8C05012(MU,MD)B12 50 1200 B 14 x 20 (2) 10 x 20

    G8C07512(MU,MD)B12 75 1200 B 14 x 20 (2) 14 x 20

    G8C07516(MU,MD)C12 75 1600 C 16 x 20 (2) 16 x 20

    G8C10016(MU,MD)C12 100 1600 C 16 x 20 (2) 16 x 20

    G8C10020(MU,MD)D11 100 2000 D 20 x 20 (2) 20 x 20

    G8C12520(MU,MD)D11 125 2000 D 20 x 20 (2) 20 x 20

    G8C15020UHD11 150 2000 D N/A N/A

    FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)

    Airflow Range

    Minimum

    Opening Size

    Filter Type

    Disposable Washable Fiber Pleated

    CFM

    in

    2

    In W.C. In W.C. In W.C.

    0 - 750 230 0.01 0.01 0.15

    751 - 1000 330 0.05 0.05 0.20

    1001 - 1250 330 0.10 0.10 0.20

    1251 - 1500 330 0.10 0.10 0.25

    1501 - 1750 380 0.15 0.14 0.30

    1751 - 2000 380 0.19 0.18 0.30

    2001 & Above 463 0.19 0.18 0.30

  • 270844-YTG-A-0407

    Unitary Products Group 7

    APPLYING FILTER PRESSURE DROP TO

    DETERMINE SYSTEM AIRFLOW

    To determine the approximate airflow of the unit with a filter in

    place, follow the steps below:

    1. Select the filter type.

    2. Select the number of return air openings or calculate the

    return opening size in square inches to determine the

    proper filter pressure drop.

    3. Determine the External System Static Pressure (ESP)

    without the filter.

    4. Select a filter pressure drop from the table based upon

    the number of return air openings or return air opening

    size and add to the ESP from Step 3 to determine the

    total system static.

    5. If total system static matches a ESP value in the airflow

    table (i.e. 0.20 w.c., 0.60 w.c., etc.,) the system airflow

    corresponds to the intersection of the ESP column and

    Model/Blower Speed row.

    6. If the total system static falls between ESP values in the

    table (i.e. 0.58 w.c., 0.75 w.c., etc.), the static pressure

    may be rounded to the nearest value in the table deter-

    mining the airflow using Step 5 or calculate the airflow by

    using the following example.

    Example: For a 75,000 BTUH furnace with 2 return openings

    and operating on high-speed blower, it is found that total sys-

    tem static is 0.38” w.c. To determine the system airflow, com-

    plete the following steps:

    Obtain the airflow values at 0.30 w.c. & 0.40 w.c. ESP.

    Airflow @ 0.30”: 1408 CFM

    Airflow @ 0.40”: 1343 CFM

    Subtract the airflow @ 0.30 w.c. from the airflow @ 0.40 w.c.

    to obtain airflow difference.

    1343 - 1408 = -65 CFM

    Subtract the total system static from 0.30 w.c. and divide this

    difference by the difference in ESP values in the table, 0.40

    w.c. - 0.30 w.c., to obtain a percentage.

    (0.38 - 0.30) / (0.40 - 0.30) = 0.8

    Multiply percentage by airflow difference to obtain airflow

    reduction.

    (0.8) X (-65) = -52

    Subtract airflow reduction value to airflow @ 0.30 w.c. to

    obtain actual airflow @ 0.38 in. w.c. ESP.

    1408 - 52 = 1356

    1. Special floor base or air conditioning coil required for use on combustible floor.

    2. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of

    the furnace jacket and building joists, studs or framing.

    *

    Cabinet clearance is "0", vent clearance is required.

    ACCESSORIES

    Propane Conversion Kit (Standard) – 1NP0366

    This accessory conversion kit may be used to convert natural

    gas units for propane (LP) operation at altitudes 0-2,000 ft.

    Conversion must be made by qualified distributor or dealer

    personnel.

    Propane Conversion Kit (High Altitude) – 1PS0467

    This accessory conversion kit may be used to convert natural

    gas units for propane (LP) operation at altitudes from 2,000 to

    8,000 ft. Conversion must be made by qualified distributor or

    dealer personnel.

    Natural Gas Conversion Kit (High Altitude) – 1PS0466

    This accessory conversion kit may be used to convert natural

    gas units for high altitude operation at altitudes from 2,000 to

    8,000 ft. Conversion must be made by qualified distributor or

    dealer personnel.

    Combustible Floor Base

    This accessory is used for downflow applications on combus-

    tible surfaces.

    17-1/2" "B" Cabinets 1FB0318

    21" "C" Cabinets 1FB0319

    24-1/2" "D" Cabinets 1FB0320

    Bottom External Filter Rack

    This accessory is used to upflow/bottom return air applica-

    tions. Packaged and sold in quantities of six (6).

    17-1/2" "B" Cabinets 1BR0312BK

    21" "C" Cabinets 1BR0316BK

    24-1/2" "D" Cabinets 1BR0320BK

    UNIT CLEARANCES TO COMBUSTIBLES

    Application Top Front Rear Left Side

    Right

    Side

    Flue

    Floor /

    Bottom

    Closet Alcove Attic

    Line

    Contact

    Upflow 1 6 0 0 0 6 Combustible Yes Yes Yes No

    Upflow

    B-Vent

    1 2 0 0 0 1 Combustible Yes Yes Yes No

    Horizontal 0 6 0 0 1 6 Combustible No Yes Yes

    Yes(See Note

    2

    )

    Horizontal

    B-Vent

    1 2 0 0 1 1 Combustible No Yes Yes

    Yes(See Note

    2

    )

    Downflow 1 6 0 0 5* 6

    1" (See Note

    1

    )

    Yes Yes Yes No

    Downflow

    B-Vent

    12 0 0 01

    1" (See Note

    )

    Yes Yes Yes No

  • Subject to change without notice. Printed in U.S.A. 270844-YTG-A-0407

    Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 246657-YTG-C-0806

    Unitary 5005 Norman

    Products York OK

    Group Drive 73069

    NOTES

  • York G8C05012(MU,MD)B12 User Manual
  • York G8C05012(MU,MD)B12 User Guide
  • York G8C05012(MU,MD)B12 PDF Manual
  • York G8C05012(MU,MD)B12 Owner's Manuals

DOC-275afce4:

Recommended for York G8C05012(MU,MD)B12 Owners: Linx 52/45, Element-MF, SOFTBANK, 327W

CARBOLITE GERO RHF 15/15, Hotblast HB1440E, PBKM, RHFE-559FTA-A-N, APEX CBT, OBF Series
  • WARM AIR FURNACEMULTIPOSITION1. ,_ :: , _ i_JJJJINSTALLER / SERVICE TECHNICIAN:USE THE INFORMATION IN THIS MANUAL FOR THEINSTALLATION / SERVICING OF THE FURNACE AND KEEPTHE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE.HOMEOWNER:PLEASE KEEP THIS MANUAL NEAR THE FURNACE FORFUTURE REFERE ...

    Model & Doc Type: AMP105-1E2 26

  • Version 1.04March 2011APEX cbtPage 1www.blazeking.comPour la version française de nos manuels S.V.P. vous référez à notre site web: www.blazeking.comAPEX cbtSOLID FUEL CATALYTIC FURNACEFor use as an add-on to electric, gas, or oil furnacesor and independent wood furnace when equip ...

    Model & Doc Type: APEX CBT 45

  • 90+ MULTIPOSITIONAL GAS FURNACE INSTALLATION INSTRUCTIONSGAS FURNACE SAFETYTable of ContentsGAS FURNACE SAFETY................................................................1INSTALLATION REQUIREMENTS................................................3Tools and Parts ............................. ...

    Model & Doc Type: WFCT 32

  • M7RL Series Downflow Condensing Gas Furnace Direct Vent (Sealed Combustion) Forced Air 95.1% AFUEINSTALLATION INSTRUCTIONSHUD Manufactured Home Construction and Safety Standards (3280.714) prohibit the use of noncertified air conditioning or heat pump equipment with this furnace. It i ...

    Model & Doc Type: M7RL Series 40

  • CLEAN BURN MODEL: CB-1400MULTI-OIL FURNACEwith CB-525-S2 BURNERIMPORTANT FOR U.S. INSTALLATIONS: All installations must be made in accordance with state and local codeswhich may differ from the information provided in this manual. Save these instructions for reference.IMPORTANT FOR ...

    Model & Doc Type: CB-1400 108

  • Energy Efficient Gas Furnace USER’S INFORMATION MANUAL DOWNFLOW/HORIZONTAL/ UPFLOW GAS FURNACE NOTE TO INSTALLER:This manual must be left with theequipment user.USER’S INFORMATION MANUAL— Do not store or use gasoline or other flammablevapors and liquids in the vicinity of this or an ...

    Model & Doc Type: 315AAV048090 8

  • 506788-01 Page 1 of 49Issue 1130This is a safety alert symbol and should never be ignored. When you see this symbol on labels or inmanuals, be alert to the potential for personal injury or death.As with any mechanical equipment, personal injury canresult from contact with sharp sheet metal ...

    Model & Doc Type: A95DF2V 49

  • 90+2-stage& *9MPT & *9MPVVariableSpeedFAN ASSISTED,!veoFU!onroaCeo,. CTCategory ryS ct IV definition.SAFETY REQUIREMENTSThis furnace ca n be installed as a direct vent furnace using outside air for combustion or the furnace can use air from inside the structure for combustion.The INLET ai ...

    Model & Doc Type: H9MPT050F12B1 68

  • Installation, Start-up, Operating,Service and Maintenance InstructionsNOTE: Read the entire instruction manual before starting the installation.TABLE OF CONTENTSREQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS2IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

    Model & Doc Type: F96CTN 76

  • IUSER'S INFORMATIONMANUALGlfHCllHC't'•• ,..aCUH'HlOama(~~"'''Jl,I.:lA;r;~'"1509001CertifiedQualityManagement SystemMODELS:33" Multi-position Gas Furnaces(Manufactured Housing or Modular Home Applications)I_~~--~-~~~~~-~~-~~~~~TABLE OF ...

    Model & Doc Type: 33" 6

Additional Information:

# Brand Model Document Type/File Pages File Size Last Checked
1 Johnson Controls Unitary Products
York DGAA Series
12 20/03
2 Reznor
RP
28 03/03
3 Lennox
LGM Series
65 03/06
4 Carrier
N80ESN Series
48 25/05
5 Alpine
Home BG802DFE
36 13/06
6 DeLonghi
ECC 2400T
7 30/04
7 Lennox
G24E SERIES
4 21/04
8 Heatmor
200 SSP
80 10/02
9 Carrier
58SE-050
17 24/03
10 Carrier
58CTA
16 2.29 Mb 18/06
11 Nortron
D SERIES
13 21/04
12 Jetmaster
16i
44 20/04
13 ShenPaz
Sintra
33 05/04
14 Intertherm
M1B Series
36 10/01
15 Bard
WG3S1-A WG3S1-B WG3S1-CWG4S1-A
59 30/05
16 Montigo
H34BF
18 09/04
17 Johnson Controls
TM8T*MP
28 26/01
18 J. A. Roby
ATF727
23 06/01
19 Unitary products group
P-HMX12F05701
32 25/04
20 Bard
WAG-Series
4 15/06
Popular Right Now:
# Brand Model Document (PDF) Pages Size Check Date
1 Samsung
HT-SB1G
25 06.02.
2 NEO
808i
53 04.04.
3 HP
1910 Series
32 05.05.
4 Trimble
3300
200 04.06.
5 Edimax
EW-7303APn v2
2 0.39 Mb 09.12.
6 A1TECH
JAZZ
27 29.05.
7 Chiayo
SQ-1016
4 11.02.
8 Jarven Health Care
OptiCell 2 PRO
20 02.06.
9 Clevo
TN120R
44 02.01.
10 Audioplex
TVC-300
2 0.05 Mb 04.06.
11 Pilz
PSWZ X1P
7 23.01.
12 Dolce Gusto
Melody 3 Automatic
6 19.03.
13 Kenwood
TH-D72A
54 20.01.
14 Orientalmotor
SCX10
8 06.04.
15 Maytag
MGR6875ADW - Gas Double Oven Range
84 16.05.
16 Gaggenau
AR401740
16 14.02.
17 Panasonic
2SC5950
2 0.32 Mb 08.04.
18 Rocktron
R20
8 0.22 Mb 24.12.
19 Bryant
394U
4 7.92 Mb 20.12.
20 JUNO
JDS5320W
8 08.05.
21 Eduard
Spitfire Mk.XVI seatbelts FABRIC
2 12.06.
22 Foster + Freeman
VSC 80
24 30.12.
23 Roland
PK-25
16 0.81 Mb 10.05.
24 Auta
hi-188
25 01.02.
25 Biostar
M7VIS
50 26.03.
26 FaceLake
FL-100
2 28.05.
Operating Impressions, Questions and Answers: