Mitsubishi Heavy Industries SC-SL4-AE Installation Manual

Installation Manual for Mitsubishi Heavy Industries SC-SL4-AE Control Panel, Control Systems (1 pages)

Specifications:

887/887337-scsl4ae.pdf file (27 Oct 2023)
  • Manufacturer: Mitsubishi Heavy Industries
  • Category of Device: Control Panel, Control Systems
  • Document: SC-SL4-AE, File Type: PDF Installation Manual
  • Updated: 27-10-2023
  • Count of Pages: 1
Download SC-SL4-AE Manual (1 pages)

Read PDF Document Online:

Data: UPD 27th October 2023

Mitsubishi Heavy Industries SC-SL4-AE Control Panel, Control Systems PDF Installation Manual (Updated: Friday 27th of October 2023 04:46:24 AM)

Rating: 4.8 (rated by 53 users)

Compatible devices: RCN-E-E3, SC-SLA3-ER, eco touch RC-EX1A, SC-SL4-AE2/1, SC-BIKN-E, RC-EX3A, RC-EXZ3A, eco touch RC-EXC3A.

Recommended Documentation:

Text Version of Mitsubishi Heavy Industries SC-SL4-AE Control Panel, Control Systems Manual (Summary of Contents)

(Ocr-Read of Document's Main Page, UPD: 27 October 2023)


CENTRAL CONTROL SC-SL4-AE, SC-SL4-BE 
INSTALLATION MANUAL
PJZ012D091A
 ● Please read this manual thoroughly and follow it carefully when carrying out installation work.
 ● Please also refer to the installation manuals for the indoor and outdoor units.
 ● The appliance must be installed in accordance with national wiring regulations.
 ● The product is a precision equipment, so please handle it with enough care to prevent the unit damage due to falling 
and being stepped on.
 ● Before touching the terminal block, turn off the power supply.
Safety Precautions
 ● Before starting installation work, read the “Safety Precautions” thoroughly in order to ensure you carry out installation 
correctly.
 ● Safety Precautions are divided into “Warning  ” and “Caution  ”.
 WARNING
: Indicates a high possibility that serious injuries or death may occur if the unit is not installed correctly.
 CAUTION
: Indicates a possibility that serious consequences may occur depending on circumstances.
Please be sure to follow the instruction.
After completing the installation, carry out a test run to conrm that no abnormalities occur, and show customers how to 
use the unit according to the User’s Manual. Please ask customers to keep the Installation Manual on hand.
 WARNING
 ● Please ask your dealer or relevant professionals to install the unit. Installing the unit by yourself may result in defects, 
which may lead to electric shocks or re.
 ● Install the unit correctly according to the Installation Manual. If any of the installation steps are not followed, electric 
shocks or re may occur.
 ● Be sure to only use the included accessories and specied parts when installing the unit. Otherwise, it may result in 
electric shocks or res.
 ● The electrical work should be performed by qualied electrical engineer, according to <Electrical Standards>, <Local 
electrical safety regulations> and wiring specication. If any of the installation steps are not followed, electric shocks 
or re may occur.
 ● When wiring, ensure solid connection and fasten specied cables securely so that terminal connections may not be 
subject to external force working on cables. Incomplete connection for terminal wiring may cause electric shock and 
resultant re.
 CAUTION
 ● Please perform grounding work. 
Please do not connect the ground wire with gas pipes, water pipes, lightning rod and telephone ground wire. 
Incomplete grounding work may cause electric shock.
 ● Please do not install the central control at the following places.
1. Oil fog lled place, oil spraying and steamy location such as kitchen, etc.
2. The place where corrosive gas such as sulfur dioxide generates.
3. The location with machine that generates radio wave. 
It may cause abnormality in the control system and abnormal running.
4. The location at risk of ammable gas leaking. 
The place where volatile combustible substance such as paint thinner and gasoline exists. 
By any chance the gas leaks and it accumulates around the equipment, it may cause ignition.
1  Applicable Models All models for Superlink
2  Accessories Please check the following accessories.
Central control 1 unit User’s manual (CD-ROM) 1 unit
Pan-head screws (M4)
4 pieces for installing on the  
control box (10mm)
Installation Manual  
(this document)
1 unit
4 pieces for embedding in a 
wall (40mm)
Installation bracket (front)  1 piece
Installation bracket (rear) 1 piece
Pan-head screws (M3)
4 pieces (8mm) for installing 
the central control
Round crimping terminal (L) Large size × 2 pieces 
Round crimping terminal (S) Small size × 6 pieces
• For SC-SL4-BE
CD-ROM (Energy consumption calculation software) 1 unit USB Memory 1 unit
3  Installation Work
Please install the central control after turning off the power for fear of electric shock.
Please arrange or protect the wiring so that excessive force is not applied to the electrical wires.
Installation Place
Please install in an indoor location that is not exposed to electromagnetic waves, water, dust, or other foreign substances.
The operating temperature range of this product is from 0°C to 40°C.
Install in a location where the ambient temperature remains within the operating temperature range.
However, if the operating temperature range is exceeded, be sure to implement corrective measures such as installation of a cooling fan.
Be aware that continued usage of this central control outside the operating temperature range can result in operation problems.
Space Required for Installation
<Opening Space for the Installation>
ø5 × 4
176
220
144
12
120
Installation 
bracket (rear)
Pan-head 
screw (M4)
Installation 
bracket (front)
Installation 
bracket (rear)
In the wall
Internal wall
Create a hole in the wall as shown in the gure above.
Be sure to check the dimensions required to correctly install 
the unit.
Insert the installation bracket (rear) into the rear of the 
wall through the hole, and secure the bracket.
Fasten the installation bracket (front) and installation 
bracket (rear) as shown in the gure above.
The top and bottom of the brackets can be easily 
identied. Be sure to check the “ UP” mark to install 
it right side up.
4  Electric Wiring
For safety reasons, please use the round crimping terminals with insulated sleeves for connecting all wires to the central control.
 ● Please do the grounding work. Please do not connect earth line with gas pipes, water pipes, lightning rods and grounding line of 
telephone.
 ● Please do not turn on the power supply (local switch) until all of the work is completed.
 ● Please wait at least two minutes after the indoor and outdoor units are turned on before turning on the power supply.
 ● Except for the central control in the gure, all of the components are obtained at the site (wires, switches, relays, power supply, lamps, 
etc.)
 ● Please be sure to build the circuit breaker which is easily accessible with building equipment’s wiring.
 ● Pease be sure to use the supplied round crimped terminals when connecting wires to the power supply terminal block and Superlink 
terminal block.
 ● Before connecting the wires, remove the cover of the terminal block. After the work is completed, x the cover of the terminal block as 
before. The cover is used to prevent electric shock due to accidental contact.
 ● Please use a gas meter or watt-hour meter, demand input device and emergency stop input device which comply with a relevant IEC 
Safety Standard.
Wiring Outline
The calculating data taken out by way of USB memory 
(accessory of SC-SL4-BE)
Emergency stop signal input
LAN
Grounding work
Local switch
L1, L2
Demand signal/Accounting 
period time input (2 points)
Power pulse input from gas meter or watt-hour meter
(8 points) (in case of SC-SL4-BE)
Power supply
AC100-240V
50/60Hz
Power 
supply
Power 
supply
Superlink system (New SL : 1 system, Previous SL : 3 systems)
Operation output
Malfunction output
Wiring Specications
Power supply wire 1.25mm
2
Local switch 10A
Superlink signal wire
(Note 1, Note 2)
Shielded wire (double-core, 0.75mm
2
 - 1.25mm
2
).
Max. 1000m per line (Max. distance: 1000m, Total wire length: 1000m)
The wire for operation output, error output, 
emergency stop and demand input
Shielded wire (double-core, 0.75mm
2
 - 1.25mm
2
).
Maximum length: 200m per system
The wire for gas meter or watt-hour meter Shielded wire (double-core, 0.75mm
2
 - 1.25mm
2
).
Maximum length: 200m per system
Grounding wire 0.75mm
2
 - 6mm
2
Note 1: When this central control is used, use a shielded wire for the Superlink signal wire. Ground both ends of the shielded wire.
(Please wire the ground of the central control at   Ground position “b” of “System Wiring” in the diagram)
Note 2: If the indoor and outdoor units connected to the network are all compatible units with New Superlink, a total wire length of 1500m per line is 
possible (maximum distance: 1000m). However, be sure to use a 0.75mm
2
 wire diameter if the total wire length exceeds 1000m. For further 
information, please contact your sales representative or dealer.
System Wiring
L1 L2
FG FG
The back of the central control
Ground 
position “a”
Ground position “b” for
Superlink system signal wire
Terminal block (two tiers)
LAN
(1)  The upper tier of Terminal Block (*)
++(*1) (*1)
(*2)

(*4)

L1 L2
DO1DO1-DO2 DO2- COMDI1 COMDI2 COMDI3 A1 B1 A2 B2 A3 B3
(*3) (*3)
(*3)
Please be sure to use the accessory terminals (S).
(Same for A2, B2, A3, B3)
Superlink system 2
Superlink system 1
Power supply 
AC100-240V 
50/60Hz
Please be 
sure to use 
the accessory 
terminals (L).
Operation 
output (O1)
Malfunction 
output (O2)
Emergency stop 
signal input (I1)
Demand signal/
Accounting period 
time input (
I2
)
Demand signal/
Accounting period 
time input (
I3
)
Superlink 
system 3
Power 
supply
Power 
supply
(*1) Power supply : DC 24V 
Maximum rating current : 40mA
(*3) No-voltage a-contact input. 
Contact capacity : DC12V, 10mA
(*2) Factory default of error output (normal operation) is closed status. You can choose “Open” 
status for malfunction output during normal operation. Please refer to the user’s manual.
(*4) When choosing the new Superlink setting, only system 1 
functions effectively.
(*5) The wire stripping length is 5mm.
(2)  The lower tier of Terminal Block
Power input from gas meter or watt-hour meter (8 points)
(in case of SC-SL4-BE)
COMPI1 COMPI2 COMPI3 COMPI4 COMPI5 COMPI6 COMPI7 COMPI8FGND FGND
Caution
●  Do not connect power supply wire to another terminal block. 
When you connect by mistake, damage and damage by re of the 
electric part are caused, and it is very dangerous. 
Please check the wiring thoroughly again before turning on power.
 ● The demand signal input is congured for two points. To congure the 
3 level setting, contact your sales representative or dealer.
 ● Please connect the gas meter or the watt-hour meter that satises the 
specication below.
•  the meter with pulse transmitter
•  the meter with pulse width of 100ms or more
 ● The energy consumption calculated by this central control does not conform to 
OIML, and there are no guarantees concerning the results of the calculations.
Notice
Please choose the new or previous setting of Superlink (SL) in the display of the main unit. (See user’s manual)
It is necessary to change if the connection network is for previous Superlink. Whether the real connection network is new Superlink or previous Superlink 
depends on the type of connected indoor unit,outdoor unit,etc. Inquire the agents or dealers for more information.
When choosing the new Superlink Communication setting, 1 system wiring can connect up to a maximum of 128 units. Be sure to connect wiring to the Superlink 
system 1. Be careful not to connect to the Superlink system 2 or 3, as the main unit will not be recognized.
Power switch
The power switch is lower front of the central control. After installation is completed, turn the power switch ON. 
Note that the central control does not start up unless the power switch is turned ON.
(It is turned ON by factory default.)
Power switch
Note
Please peel off the protection sheet of the screen when you pass the central control to the customers.
Before you mount the upper case, please peel off the sheet.
After checking the wiring and doing power switch operation, when the screen is not displayed, please contact 
the shop where the central control was purchased. This product consists of the exclusive parts, and you can not 
exchange the electrical equipment. Please do not disassemble other than what is stated in this instruction manual.
Other Information
•  This central control is electronic and independently mounted control.
•  The type of this central control is automatic action for which the manufacturing deviation and the drift of its operating value, operating time or operating 
sequence have not been declared and tested under the standard.
•  The actions of this central control are full-disconnection on operation, a trip-free mechanism which cannot even momentarily be reclosed against the fault, 
an action which can only be reset by the use of a tool, an action that does not require any external auxiliary energy source of electrical supply for its intended 
operation, and electronic disconnection on operation.
•  The rated impulse voltage (impulse withstand voltage) is 2500V.
•  The surface of touch panel and front cover produce an increase of temperature of about 15 degrees.
•  Purpose of control is operating control.
•  The lifetime of the keying of touch panel is ten million times. The lifetime of LCD is about 80,000 hours.
•  Control pollution degree is 2.
•  Ball pressure test temperature : 75 ºC (front cover)
•  Voltage and current declared by the EMC tests : AC85V:172mA, 200V:103mA
•  The MAINTENANCE MENU is provided for dealers and qualied professionals responsible for maintaining the central control units. When logging in 
with a normal operator’s ID, you are not permitted to operate the MAINTENANCE MENU. Please refer to the user’s manual. 
Please do not disclose the ID and password to anyone except operators. ID : MHI, Password : 123456
  The default ID and password can be changed. Please refer to “MAINTENANCE USER SETTING” in the user’s manual.
(1)  In case of installing on the control box
•  Please use the control box of the size of 300mm × 400mm × 120mm 
or larger. 
•  Please be sure to lock the control box to protect persons from electric 
shock. Avoid usage of heat-retaining materials and heat-insulating 
materials because these can result in heat buildup and adversely 
affect the operation of the central control.
Caution
Please do not install devices that can cause the ambient 
temperature to rise in the same control box. Also, do not install 
multiple controllers in the same control box. These can cause heat 
to build up and result in false operation. If multiple central control 
must be installed in the same control box, take corrective measures 
to ensure that the temperature in the control box does not rise above 
40°C such as by installing cooling fans.
<Service space>
500
100
Front of the central control
500mm or larger
Bottom of the central control
100mm or larger
(2)  In case of embedding in a wall
Be sure to use the attached installation brackets. Alternatively, you 
can use SLA3R-BX for SC-SL3N. Please be sure to use for protecting 
persons from the electric shock. Please check that the sufcient space is 
available in the wall. When the inside of the wall is divided and have a 
cavity, please create space more than 0.08m
3
. Refer to the table below. 
If there is partition on the left, right, top and bottom of the central 
control, please create a space that is 105mm or deeper.
a (height) 
(mm)
b (width) 
(mm)
c (depth) 
(mm)
space (m
3
)
Example1 900 800 110 0.08
Example2 1800 400 110 0.08
Example3 1000 400 200 0.08
Minimum 600 or larger 400 or larger 110 or larger
<No partition> <With partition>
105mm or 
larger
Inner wall 
materials
Beam of 
building
Lead-in 
cable

a

b
c
Partition
Internal 
wall
Central 
control
Installation Position
Install the central control so that the center of the screen will 
be at the same height as the eye level of people who will 
frequently use the unit.
The recommended position is that the center of the screen 
becomes within +10, -30 degrees from eye level.
5cm
(30cm)
10°
Central control
30°
17cm
Installation procedure
(1)  Remove the upper case
1Take out two screws using a 
cross slot screwdriver. (Do not 
lose the screws)
2Pull the upper case a little 
forward and push above. Then, 
upper case can be removed.
Caution
Please do not install 
facing upward or at 
a slant.
Allowed Not allowed Not allowed
 ● Embed signal wire and power supply wire in the 
wall beforehand.
 ● Connect wires to the terminal block.
 ● Conrm power supply voltage and connect 
correctly.
3
2
1
(2)  Installation outline
 ● Be sure to use the attached installation 
brackets. 
Wall
LCD
Central 
control
Installation 
bracket (front)
Installation 
bracket 
(rear)
Upper 
case
M3 pan head screw × 4 positions
•  Fasten the central control to the front side of the control box or a hole 
in the wall using the M3 screws.
•  Wire separately the power supply wire and the signal wire for 
preventing malfunctions.
6.4
3.7
5.5 (less than 6.3)
3.2 (for M3)
PJZ012D091A_EN.indd   1 2015/02/10   15:27:42





DOC-13bf4a40:

Recommended:
DVP3020K, DPL930VD, FLATBEAM DUO 48x8W RGBW, IC ?2A

RS-485, SINUMERIK 840Di, 131-440, Aeware in.k200 series, TYXIA 6410
  • SEA-FIRE MARINE – USA SEA-FIRE EUROPE, LTD Baltimore, Maryland Hampshire, United ...

    Model & Doc Type: 131-440 12

  • m2/m2-Spy/m2+ Instructions RI.8B.M4.83 © Danfoss 09-2002 1Electronic RefrigerationInstructionsBedienungsanleitungInstructionsm2/m2-Spy/m2+Dimensions Abmessungen DimensionsMounting Montage ...

    Model & Doc Type: m2 8

  • 0522 - Printed in Germany 9.0245.04Field of applicationThe BA-Filling-Combi type 6628 automatically lls and rells central heating installations. The integral BA back-ow preventer complying with the European Standard EN 1717 prevents the backow of heating water into the po ...

    Model & Doc Type: BA-Filling-Combi 6628 2

  • © 2014 SPX CORPORATION1Form No. 1000773 Rev. 0 August 12, 2014 These operating instructions must be read and thoroughly understood for the safe commissioning, operation, and maintenance of the Motion control system. The following procedures must be performed by qualified, trained personnel who ar ...

    Model & Doc Type: Power Team MCS Series 48

Additional Information:
# Brand Model Document Type/File Pages File Size Last Checked
1 ABB
Relion 615 series
80 22/10
2 Fagor
CNC 8060 LASER
12 23/03
3 Eaton
SVS/12
138 25/02
4 PAT
DS 50
51 23/11
5 Siemens
Simatic S7-300
108 16/01
6 PROEL
ZONE8
32 26/10
7 Abekas
AirCleaner
106 03/12
8 EKOVENT
EKO-KE8
5 16/12
9 Firestone
2554
4 03/03
10 Raven
SmarTrax
20 19/01

Popular Right Now:

# Brand Model Document (PDF) Pages Size Check Date
1 Haier
BCD-216
14 2.49 Mb 03.12.2023
2 RCA
CC6384/CC6394
128 1.88 Mb 10.11.2023
3 Fisher & Paykel
88433
4 0.41 Mb 22.12.2023
4 DFI
848P-AL
114 17.02.2024
5 Zibro
S 3637
2 0.82 Mb 19.12.2023
6 DGT
DGT2010
14 11.09.2023
7 Omega
24
48 29.02.2024
8 JVC
VN-H37U series
4 06.02.2024
9 ring
RAC750
2 05.01.2024
10 Big Dog
2006 K-9
100 23.11.2023
Operating Impressions, Questions and Answers: